SANS 10400-N Safety Glazing: Where Safety Glass Is Mandatory in South Africa

The six locations that make safety glass compulsory, the thickness each one demands, and the deflection limits that follow.

SANS 10400-N · SANS 1263-17 minFor Architects, quantity surveyors, contractors and homeowners

SANS 10400-N is the deemed-to-satisfy glazing rule under the National Building Regulations, read together with SANS 1263-1 for impact performance. It does not describe a preference. It describes where annealed glass is prohibited, and a building inspector can require the glazing to be replaced.

The position in one paragraph

SANS 10400-N sets out where glazing must resist human impact, and SANS 1263-1 defines what that resistance means in a laboratory. Together they produce a single instruction: in a defined set of locations, the glass must be safety glass of Class A, and the rest of the system must be engineered so the glass is never loaded beyond what it was tested for. A pane that satisfies neither is a liability that follows the installer, the fabricator and the professional who signed the drawing.

The six mandatory safety glazing locations

LocationWhat triggers itMinimum requirement
Doors and side panelsAny glazing within 300 mm of a door frame openingClass A safety glass
Low-level glazingAny pane installed lower than 800 mm from the finished floor levelClass A safety glass
Bathrooms and wet areasAll shower cubicles, bath screens and panels within 2.1 m of the floorToughened safety glass, minimum 6–8 mm, or 10 mm for frameless; laminated safety glass also accepted
Overhead and roof glazingSkylights, rooflights, canopies and any glazing above head heightLaminated safety glass, so shards are retained on failure rather than falling
Frameless doors and balustradesStructural glass with no frame to hold the panel in placeToughened or toughened laminated: 10–12 mm for post systems; 12–15 mm and heavier for base-channel cantilevered systems, per SANS 10160 line loads
Public and hazard areasMirrors in gyms, dance studios, schools, malls and change roomsFoil-backed safety mirror or mechanically secured safety glass

SANS 10400-N, with impact performance per SANS 1263-1.

The mistake we are called to fix most often

3 mm or 4 mm annealed float glass in a door or a door-side panel. It is cheap, it is what a bakkie glazier carries, and it breaks into large shards at the exact height a child's hand rests. It fails the 300 mm door rule and the 800 mm low-level rule simultaneously. There is no repair for it other than replacement.

Choosing the right assembly for the opening

Minimum compliance is not the same as a correct specification. The application decides whether toughened, laminated or toughened laminated is right: toughened glass is stronger but releases into small blunt dice on failure, while laminated glass holds its shards on the interlayer and stays in the opening. Overhead, in a public space, or anywhere a failed pane could fall on a person, the interlayer is what protects you.

Specification by application

ApplicationTypical specificationWhy
Frameless shower door10 mm toughened, polished edges, 8 mm minimum for a framed enclosureWet-area rule plus the bending load carried by exposed hinges
Aluminium sliding door glazing6 mm toughened, or 6.38 mm laminated to a 300 mm door-side zoneDoor and side-panel rule; laminated also satisfies the security and solar brief
Shopfront and entrance screens10–12 mm toughened; laminated in the pedestrian impact zonePublic occupancy and trolley/traffic impact
Glass balustrade, post system10–12 mm toughened laminatedLine load shared between the posts and the glass
Glass balustrade, base channel12–15 mm+ toughened laminated on a structural base shoeCantilevered panel takes the full line load at the base
Skylight or rooflight6.38 mm or 8.38 mm laminated, or a sealed DGU with a laminated inner paneOverhead glazing must retain its shards
Gym or studio mirror4–6 mm mirror on a foil backing, mechanically fixedImpact in a public space must not release flying glass
Free-standing glass partition10 mm toughened, or 12 mm toughened laminated for a full-height spanLow-level glazing and human impact

Deflection is part of the glazing rule, not a separate engineering problem

Glass only performs as tested if the frame holds it within its design deflection. Over-deflect the framing and the edge stresses rise, the sealant opens and a water-penetration test fails even though the glass itself is correct. AAAMSA deflection limits exist precisely so the glazed opening stays within the performance that was certified.

Deflection limits

ConditionLimit
Aluminium framing under wind loadL/175 of the span, or 20 mm, whichever is less
Exposed single glass edgeL/65 of the span

What voids compliance, whatever the glass

  • 01A door or door-side panel glazed in annealed float glass, regardless of thickness.
  • 02A wet-area panel installed without toughened or laminated safety glass, even if it looks heavy.
  • 03A mirror in a gym or studio fixed with adhesive only, with no mechanical restraint.
  • 04A base-channel balustrade built from a panel thinner than the line load demands.
  • 05A safe pane of glass held in a frame that deflects beyond L/175 under the site's wind load.
Questions we answer most often

4 answers on this standard

What we issue

Documentation that closes a project out

Fabricated at our Meadowdale facility in Johannesburg and installed nationwide. Every scope that requires sign-off leaves here with the paperwork that proves what was built.

Glazing Certificate of Conformance

Signed by a SAGGA-registered competent person, naming the glass type, thickness, class and location of every pane we supplied.

AAAMSA performance submission

Wind-load, deflection and water-penetration certification for the aluminium system as installed, with the test classification quoted.

Form 4 submission support

Documentation pack prepared for the local authority on request, so sign-off is not held up by missing glazing evidence.

Fabrication drawings and cut sheets

Dimensioned drawings, glass schedules and profile cut lists issued from our Meadowdale facility against the approved revision.

Thermal and solar schedule

U-value and SHGC values for the specified assemblies, tabled against the climatic zone the project falls in.

Installation and fixing schedule

Anchor type, centres, sealant and drainage details per elevation, so the rated system is not compromised on site.